Features - Rugged 4U rack height
- True on-line uninterruptible power supply
- Global input power
- Input isolation transformer
- True sinewave output
- User selectable output voltage
- Automatic bypass
|
 |
|
| Input Voltage | 92-127 VAC, 198-254 VAC(automatically sensed and selected) | | Input Voltage Rating | 120 V / 240 V | | Maximum Input Current Rating | 25 A (maximum at 120 VAC) | | Input Frequency | 40 - 70 Hz autosensing; 50/60 Hz compatibility | | Line Sag / Surge Range Without Going to Battery | 80-140 / 160/264 VAC (If total load is kept under 75%) | | Input Power Factor | >0.95 typical | | Output Rating | 3000 VA / 2100 W | | UPS Output Voltage | 120 V nominal ±3% | | Output Voltage Settings | UPS: 100/110/115/120/127 VAC; user selectable, max 5% total harmonic distortion (THD) full non-linear load (Note: The UPS output rating should be reduced by 10% for the output voltage setting of 100 VAC) | |
| Output Frequency | 50 or 60 Hz (fixed selectable, or synchronized to input) | | Output Overload | 200% for 8 cycles; 130% for 10 seconds with transfer to bypass | | Transfer time to Battery | uninterrupted (none) |
|
| Reserve Time | 5 minutes at full load | | Recharge Time | 5 hours to 95% after full load discharge | | Rating | 72 VDC / 9 ampere-hours (Ah) (Note: Approximate Ah at 20- hour discharge rate) | | Type | Valve Regulated, non-spillable, lead acid | | Replacement Time | < 5 minutes |
|
| Ambient Temperature | 0°C to 40°C / 32°F to 104°F operating for altitudes 0-3,000 m / 0-10,000 feet above sea level; -15°C to 50°C / 5°F to 122°F non-operating | | Relative Humidity | 0 to 95% non-condensing | | Operating Altitude | Full rating up to 3,000 m / 10,000 feet when operated within the temperature range specified above, 15,000 m / 50,000 feet non-operating | | Audible Noise | ‹ 50 dBA at 1 m / 3.3 feet |
|
| Dimensions (HxWxD) | 17.7 cm x 43.2 cm x 61.0 cm / 7 inches x 17 inches x 24 inches | | Weight | 115lbs / 52 kg (approximately) | | Input Power Cord | 1.8 m / 6 foot with L-6-30 plug | | Output Receptacles | Six 5-20R, one L-5-30R |
|