DRS Technologies Masthead 

3000w-ups

3000VA / 2100W UPS
3000TR-IV


A rugged/deployable uninterruptible power supply (UPS).

pdfDownload Product SheetUPSI GSA
FEATURES
  • True On-line UPS
  • Global Input Power
  • Remove Battery Pack or Replace UPS Electronics Module without Interrupting the Load
  • Input Isolation Transformer
  • True Sinewave Output
  • Automatic/manual Bypass
  • Battery Start
  • Optional external extended runtime battery module.

Electrical
Input Voltage Range100/120/220/240 VAC (automatically sensed and selected)
Input Frequency 40-70 Hz autosensing
Max Input Current at 120 VAC25 amps
Input Power Factor›0.95 typical
Output Ratings: UPS3000VA/2100 W
Output Voltage100/110/115/120/127 VAC, ±3%; sinewave; max 5% THD full non-linear load
Output Frequency50/60 Hz ±3 Hz
Max Output Current25 amps
Output Overload200% for 8 cycles; 130% for 10 seconds then transfer to bypass
Transfer Time to BatteryUninterrupted (none)
Battery
Reserve Time5 minutes at full load
Recharge Time5 hours to 95% after full load discharge
Rating72VDC/9AHr
TypeValve regulated, non-spillable, lead acid
Environmental
Ambient Temperature0°C to 40°C operating 
-15°C to +50°C non-operating 
Relative Humidity0 to 95% non-condensing
Operating Altitude0 to 3000 meters
Audible Noise‹ 63 dBA at 1 meter
Mechanical
Dimensions
UPS Electrontics Module
(LxWxH inches)
5.25 x 17 x 19
UPS Electrontics Module
(LxWxH mm)
133 x 432 x 483
Battery/Bypass Module
(LxWxH inches)
5.25 x 17 x 20
UPS Electrontics Module
(LxWxH mm)
133 x 432 x 508
Weight
UPS Electronics Module14.1kg (32 lbs)
Battery/Bypass Module52.3kg (100 lbs with battery)
Battery Weight17.3kg (40 lbs)
Tomorrow's Technology. Today.
>
© 2009 Property of DRS Pivotal Power, All rights reserved. User Agreement and Disclaimers