- True On-line UPS
- Global Input Power
- Remove Battery Pack or Replace UPS Electronics Module without Interrupting the Load
- Input Isolation Transformer
- True Sinewave Output
- Automatic/manual Bypass
- Battery Start
- Optional external extended runtime battery module.
|
 |
|
| Input Voltage Range | 100/120/220/240 VAC (automatically sensed and selected) | | Input Frequency | 40-70 Hz autosensing | | Max Input Current at 120 VAC | 25 amps | | Input Power Factor | ›0.95 typical | | Output Ratings: UPS | 3000VA/2100 W | | Output Voltage | 100/110/115/120/127 VAC, ±3%; sinewave; max 5% THD full non-linear load | | Output Frequency | 50/60 Hz ±3 Hz | | Max Output Current | 25 amps | | Output Overload | 200% for 8 cycles; 130% for 10 seconds then transfer to bypass | | Transfer Time to Battery | Uninterrupted (none) |
|
| Reserve Time | 5 minutes at full load | | Recharge Time | 5 hours to 95% after full load discharge | | Rating | 72VDC/9AHr | | Type | Valve regulated, non-spillable, lead acid |
|
| Ambient Temperature | 0°C to 40°C operating -15°C to +50°C non-operating | | Relative Humidity | 0 to 95% non-condensing | | Operating Altitude | 0 to 3000 meters | | Audible Noise | ‹ 63 dBA at 1 meter |
|
| Dimensions | | UPS Electrontics Module (LxWxH inches) | 5.25 x 17 x 19 | UPS Electrontics Module (LxWxH mm) | 133 x 432 x 483 | Battery/Bypass Module (LxWxH inches) | 5.25 x 17 x 20 | UPS Electrontics Module (LxWxH mm) | 133 x 432 x 508 | | Weight | | | UPS Electronics Module | 14.1kg (32 lbs) | | Battery/Bypass Module | 52.3kg (100 lbs with battery) | | Battery Weight | 17.3kg (40 lbs) |
|