FEATURES - Meets MIL-S-167-1 and 901D
- Shock & Vibration
- Removable Battery Pack
- Rugged 3U Rack
- Height Design
- Input Isolation
- Transformer
- Input Power Factor Correction
- 2000VA True Sinewave
- Output Power
- Automatic Bypass
- Switch
- Single Point Ground
- Rackmount Slide Kit Available
|
 |
|
| Voltage | 120VAC, +10% -30% | | Frequency | 45-65Hz autosensing; | | Max Input Current | 16 amps | | Power Factor | >.98 | | Power Cord | Detachable 6' with 5-15P Plug |
|
| Rating | 2000VA/1400W | | Voltage | 120 VAC,±3%; sinewave; max 3% THD linear load | | Frequency | 50/60 Hz±3Hz auto selected (synchronized to input);±0.1 Hz ( free running) | | Current | Rated @ 16.7A rms | | Max current | rated @ 50A | | Crest Factor | 3.0 | | Overload | 150% for 60 seconds | | Transfer Time to Battery | none | | Receptacles | Six (6) 5-20R |
|
| Reserve Time | 5 minutes at full load (extended reserve time available) | | Recharge Time | 8 hours to 90% after full load discharge | | Rating | 12VDC / 5AHr | | Type Sealed, Maintenance-free |
|
| Ambient Temperature | 0° C to 40° C operating -20° C to 40° C non-operating | | Relative Humidity | 0 to 90% non-condensing | | Operating Altitude | Full rating up to 3000 meters | | Altitude Derating | -10% per 1000 meters above 3000 meters | | Audible Noise | < 50 dBA @ 1 meter |
|
| Dimensions | | (H x W x D) | 133 mm x 483 mm x 610 mm (5.25" x 19" x 24" ) | | Weight | | UPS with Battery | 46 kg (101.4 lbs) | | Removable Battery Pack | 13.8 kg (30.4 lbs) | | Shipping Materials | 5.9 kg (13.0 lbs) |
|